Stair Calculator

Lay out a straight staircase: risers, treads, total run and stringer length from the floor-to-floor height — with warnings when a dimension breaks residential code.

By Dr. Priya Nair, science writer and former university physics lecturer · Updated

Stair Calculator

Enter any 3 known values — the others are solved as you type. Change units at any time.

Fill in the values you know.

How to use this calculator

Measure the total rise from finished floor to finished floor. Enter it with a tread depth (10 inches is pre-filled, the IRC minimum), then try numbers of risers until the riser height is comfortable — 7 to 7¾ inches for homes. If you enter a maximum riser height instead of a count, the number of risers is shown with a note to round it up; enter that whole number to get the final layout.

Every other combination works as well: from a fixed run available on the floor plan and the total rise, the calculator gives the tread depth and angle for a chosen number of risers. Warnings appear under the riser and tread fields when values fall outside the IRC R311.7 limits.

The formula

r = H / n
L = (n − 1) × d
S = √(H² + L²)
θ = atan(r / d)
H
total rise (floor to floor)
n
number of risers
r
riser height
d
tread depth (run per step)
L
total run
S
stringer length (hypotenuse)
θ
stair angle

Worked example

The finished floor-to-floor height is 105 in (8 ft 9 in). You plan 14 risers and 10-inch treads.

  1. Riser height = 105 ÷ 14 = 7½ in — under the 7¾-inch IRC maximum.
  2. There is one fewer tread than risers: total run = 13 × 10 = 130 in.
  3. Stringer length ≈ √(105² + 130²) = 167.1 in; stair angle = atan(7.5 / 10) = 36.9°.

Cut stringers from 16-ft boards (at least 14 ft of usable length) and allow 10 ft 10 in of floor space for the run.

Residential stair limits (IRC R311.7)

DimensionRequirement
Riser height7¾ in (196 mm) maximum
Tread depth10 in (254 mm) minimum, measured nosing to nosing
Variation within a flight⅜ in (9.5 mm) maximum between largest and smallest
Headroom6 ft 8 in (2032 mm) minimum
Nosing¾–1¼ in where treads are under 11 in

Local codes may differ; commercial stairs (IBC) allow at most 7 in risers and need 11 in treads.

Assumptions and limits

  • A straight flight with equal risers, and the top tread is the upper floor (so there is one fewer tread than risers).
  • Stringer length is the hypotenuse of rise and run; add the extra needed at the top and bottom cuts when buying lumber.
  • The rule of thumb 2r + d ≈ 24–25 in gives comfortable stairs.

Frequently asked questions

How many steps do I need for a 9-foot rise?

108 in ÷ 7¾ in = 13.9, so at least 14 risers of 7.71 in each, and 13 treads.

What is a comfortable stair angle?

Between about 30° and 37°. Residential maximums (7¾ in risers on 10 in treads) give 37.8°.

Why is there one fewer tread than risers?

The top step is the upper floor itself, so the final riser leads onto the landing rather than onto another tread.